STANDARD SYSTEM
The Protect RCS range of systems has been preconfigured with a number of the most commonly requested features built-in as standard. These systems are available “off-the-shelf” with standard drawings and standard user documentation.
Standard configuration
- Single system with building block modular design
- Internal rectifier input switch Q1
- 6-pulse rectifier bridge with input isolation transformer
- Digital control card GCAU
- Output filter L1-C1 ripple voltage <5 % RMS without battery
- Rectifier F1 fuse and rectifier shunt R2
- Blocking diode V21
- Multi-functional LCD with 2 LEDs indicate the system status
- Tropicalized control electronics boards
- Common fault remote alarm
- Floor mounted cabinet with external IP21 protection and IP20 with open doors
- Cabinet colour RAL 7035
- Power and control cable marking
- Detailed 3-D layout and component marking presented on rear door
- Door able to open to180° with three key locks
- Bottom cable entry
- Input / battery / output terminals X1, X2 and X3
- » Standard labeling / nameplate
OPTIONS
The standard system can be enhanced by the additional options. To provide exact solutions for each application, we offer a wide range of options:
System
- Parallel redundant configuration with load sharing
- Special mains input voltages (180 – 690 V) and frequency 60 Hz
- DC ripple filter 1 % & 0.1 %
- 12 pulse rectifier with isolation transformer
- Rectifier input MCB or fuse
- Battery MCB, fuse or switch in rectifier
- Battery MCB or fuse box
- Load MCB, fuse or switch
- Diode dropper
- DC distribution
- Battery installed inside the rectifier cabinet
Alarms / signaling / measurement
- LED alarm indicators in front panel
- Relay cards 2 x 8 free contacts
- Additional analog meters
- Low electrolyte level alarm
- Audible alarm
- Temperature charging compensation sensors & cables
- Temperature alarm
- High DC ripple voltage alarm
- Cable drop compensation
- Battery circuit failure alarm
- Ground fault alarm
- High rate interlock
Control options
- Remote rectifier shutdown command
- Remote forced floating charge command
- Remote room fan control
- Remote alarm reset
- Remote high rate charge command
Communication
- RS232 / RS485 interface
- RS232 / RS485 Modbus protocol
- TCP / IP interface
- Protocol converters (Profibus DP, J-bus)
- Monitoring and management software
- Modem
Mechanical
- Interior cabinet light, AC single phase socket & cabinet heater
- Protection up to IP54
- Special colour
- Vermin proof protection plates
- Low smoke wiring (halogen-free)
- Special markings
- Top cable entry
- Air filters at air inlet
- Ventilation 100 % redundant
Additional options are available on request